MinePwr-MPC-R35921
Category : PORTABLE SUBSTATIONS
Description
1000KVA 5KV SUBSTATION
Enclosure:
- Built as per Adria mine duty standard
- Built for vertical handling and lifting
- NEMA 2 cabinet
- Drip proof design, suitable for underground mining
- Sand blast surface preparation and epoxy painted
- Standard and easy to change replacement parts (doors, accessories, etc.)
- Dimensions and approximate weight:
- 135’’W x 48’’D x 65’’H
- 9 000 lbs
General information:
- Standard production testing
- All control wiring is SIS type as per CSA C22.1 #31 regulation (switchgear)
- CSA certification
- CAN CSA M421 compliant (mines and quarries)
Section 1
5kV primary disconnect switch:
- 5kV 600A load break switch c/w DIN fuses (45mm x 292mm)
- Store Energy Mechanism (SEM)
- Blown fuse tripping device
- Padlock provision
- Load break will trip in the event of a problem with NGR (SE-330) to comply with CEC2018
- 5kV 400A vacuum contactor
- 1x 4160/120V control voltage transformer with fuses
- Kirk-key interlock between 5kV switch door and switch handle, to prevent access when energized
- Recessed operating handle, to prevent breaks during handling
- Removable protecting mesh barrier for safe fuse replacement
- Visualization window to see 5kV switch state (safety glass)
- Top entry 5kV cable connection compartment behind interrupter
Section 2
4160/600-347V « Delta-Wye » transformer:
- Dry type power transformer
- Mine duty transformer
- 1000kVA
- Class H insulation 220°C
- Copper windings
- 150°C rise
- Primary: 4.16kV Delta) BIL: 30kV
- Secondary: 600/347V (Wye) BIL: 10kV
- Taps: 4x 2.5% (2FCAN + 2FCBN)
- IZ: 5% (est)
- Splashproof ventilation louver with metal mesh protection behind
- Neutral grounding resistor (NGR) 69 Ohm, 5A cont.
- ER600V StartCo sensing resistor with CT
- CT’s and PT’s installed at the transformer secondary
Section 3
600V distribution panel:
- 6x 225A 3 poles c/w shunt trip 25kA feeder breakers
- 2x 400A 3 poles c/w shunt trip 25kA feeder breakers
- Padlock hasp on all 600V breakers
- 8x SE-105 ground fault protections c/w 200:5 CT on shunt trip equipped feeder breakers
- SE-330 NGR monitoring
- 1x digital power meter with CT and PT for metering (installed in control section)
- Realtime metering: V (L-L), V (L-N) A, PF, HZ
- 3 phases current are always visible simultaneously without user action required
- Metering (average): A (demand)
- Metering (max): V (L-L), V (L-N), A
- Metering (min): V (L-L), V (L-N), A
- RS-485 (Modbus RTU) communication
- Realtime metering: V (L-L), V (L-N) A, PF, HZ
- 120/240V 10kVA auxiliary distribution (dry type) 4x 15A and 4x 20A cct recessed including 1x GFCI 120V 20A outlet with raintight cover
- 1x « 5kV contactor opened » green LED indicator light
- 1x « 5kV contactor closed » red LED indicator light
- 1x « 5kV contactor opened » pushbutton
- 1x « 5kV contactor closed » pushbutton