Defender-LV-J1D-R35529
Category : POWER TAKE-OFF (PTO)
Description
SOFTSTART PANEL AND AUXILIARY DISTRIBUTION (1B LEFT)
Electrical Specifications :
- 600V distribution including:
- 1x main circuit breaker 600V 600A (with lugs for 500MCM) c/a rotary handle on front
- 1x thermomagnetic branch circuit breaker 600V 200A 3 poles c/a rotary handle on front
- 2x branch switches 600V 400A 3 poles c/a rotary handle on front
- 3x 250A branch fuses
- 1x thermomagnetic branch circuit breaker 600V 100A 3 poles c/a rotating handle on front
- 1x digital measuring module
- Current/voltage/power display
- RS485 communication
- 3x CTs 600/5 at the entrance to the panel
- 2x PTs 600/120 c/a protections
- 2x Softstart 125HP starters including:
- Softstart 125HP WEG SSW07 c/a front panel control keypad
- Push buttons: Start, Stop and Reset
- Green LED Indicator Lights (LED) for Starter Running and Fault Indication
- LB for teak cable connector with 1-1/4 in. hub for each Softstart outlet c/a close nipple, sealing ring, lock nut and 1-1/4 in. bushing
- 1x timer for controlling Softstarts
- 1x PTO 200A output including:
- Contactor 600V 225A
- 600V 225A jumbo socket mounted on box
- 45° down housing for each PTO socket
- Protective cap for each PTO socket
- “Ground fault / ground check” module
- Green LED indicator light (LED) for power output indication
- Auxiliary distribution including:
- 1x transformer 3kVA 600 120/240V ac primary and secondary protection
- 1x 8ccts c/a distribution panel 8 branches 15A
- 1x 120V 15A GFCI/GFCI outlet with waterproof cover on the outside
Features of the enclosure:
- NEMA 2 Steel Cabinet
- Folded sheet metal base with openings for transport with fork lift
- Roof lifting anchor
- Drip-proof housing designed for mining use
- Cabinet cleaned with sandblasting and gray epoxy paint
- Standard replacement parts available and easy to replace (doors, accessories, etc.)
Approximate dimensions and weight:
- 76 1/4’’ L x 30’’ P x 82 1/4 H
- 1500 lbs
- Certification CSA