FlexiGear-FS-R30720
Category : SWITCHGEAR
Description
12.5 KV Breaker Switch combo:
Enclosure:
- Self-supported cell enclosure, metal-enclosed type NEMA 1 gasketed
- Sand blast surface preparation and epoxy painted
- Removable non-magnetic connector plate
15kV Breaker:
- Type : Vacuum, indoor, 3 poles
- Mounting : Fixed
- Rated voltage : 15 kV rms
- FLC : 200 A
- Isc : 20 kA
- Max. Sym. Interrupt & STC: 20 kA rms
- Close & Latch : 52 kA rms
- Lightning Impulse Withstand (BIL) : 95 kV Crest
- Low Frequency Withstand (Hi-Pot) : 36 kV rms
- Rated frequency : 60 Hz
- Control voltage : 24 Vdc
- Four auxiliary contact for client use : 2 NO – 2NC
15 kV Load break Switch :
- Rated voltage : 15 kV
- Rated current : 200 A
- Impulse test voltage : 95 kV
- Momentary rating asymmetrical : 40 kA eff
- Fault-closing rated current asymmetrical : 40 kA eff
- Short time current symmetrical : 25 kA eff./ 3 sec.
Other electrical components:
- 3 x Current Transformer / 400:5A 0.3B1.8
- 1 x Test switch, Isoelectric, 4PCCG
- Protection Relays Schweitzer no. 751A
- 3 x Voltage indicators on incoming side of the disconnect switch
- Tin plated copper bus bar and 15 kV insulator design for 20 kA rms sym short circuit
- 50mm x 6mm copper bus bar for grounding
- 2 x Copper braids for doors grounding
- 1 x Charger 24 Vdc (10 A)
- 2 x 24V battery
- 6 x Grounding ball stud with insulating boot
- 1 x Kirk Key with chain to close shelter/container doors supplied loose matching kirk key on the switch handle preventing doors from being opened when transformer is under power
General information :
- Standard production testing
- All control wiring is SIS type as per CSA C22.1 #31 regulation (switchgear)
- Schematic drawings included (Adria standard)
- Installation & maintenance manual included
- Danger signs, Arc-Flash signs, etc.
- CSA approval included
- CAN CSA M421 compliant (mines and quarries)
- This design is already type tested (Corona & BIL test from previous order)