MinePwr-HY-J34379
Category : PORTABLE SUBSTATIONS
Description
1250kVA Mine Power Center / 2 types of distributions
Electrical specifications
- Primary protection: Vacuum circuit breaker
Transformer:
- Primary voltage: 13 800V /4 160V
- Primary BIL: 95/60kV
- Secondary voltage: 600V / 347V
- Secondary BIL: 10kV
- Power: 1250kVA
- Dry type transformer
- Winding: Aluminum
Secondary distribution:
- Segregated feeder breakers
- 6x feeder breakers 400A
- 2x feeder breakers 200A
- PTO outputs
- 3x PTO 225A
- 600V distribution panel
- 1x Main breaker 1200A
- 1x feeder breaker 600A
- 2x feeder breakers 400A
- 2x feeder breakers 200A
- 1x feeder breaker 30A
- 1x feeder breaker 15A
General specifications
- NEMA 2
- Approximate dimensions
- 190’’ L x 90’’ D x 94’’ H
- Certification: CSA