Product Catalog

MinePwr-HY-R34379

Description

MONOBLOC 1250KVA SUBSTATION WITH DYN1 SEGREGATED 600V DISTRIBUTION

Section 1

15kV main switch including:

  • 1x fixed electrically operated vacuum circuit breaker
    • 15kV, 600A, 20kA
    • Loss of voltage protection (the circuit breaker opens if it loses its control voltage)
    • Tripping of the 15kV circuit breaker, in the event of breakdown of the neutral resistance or earth leakage (SE-325)
  • 1x control transformer
    • 1x 5kV and 1x 15kV (to be changed depending on the voltage used)
    • With primary and secondary fuse protection
  • 3x LED high voltage presence indicators installed directly at the 5kV switch input
  • 3x MALT sockets on each phase (load side of the 5kV switch) and 1x on the MALT outside the cabinet
  • Kirk-key interlock between the door and the switch, to prevent opening under voltage
  • Removable protection grid, to secure the changing of fuses
  • Window (safety glass) for displaying the status of the switch contacts
  • Option of a self-reclose included (see description below)

Section 2

Transformateur 13800-4160 / 600-347V « Delta-Wye » incluant :

  • Dry distribution transformer:
    • Compliant with NRCan2019 efficiency standards
    • 1250kVA
    • Class H insulation 220°C
    • Aluminum winding
    • 150°C temperature rise
    • Primary: 13.8/4.16kV (Delta) BIL: 95/60kV
    • Secondary: 600/347V (Wye) BIL: 10kV
    • Primary taps: 4-2.5% (2FCAN + 2FCBN)
    • IZ: 6% (est.)
  • Neutral resistance 69Ohm, 5A continuous
  • Tertiary winding 15kVA 120/208V
  • SE-325 neutral resistance monitoring relay with ER 600 and CT
  • Current and voltage transformers, installed on the secondary side of the transformer
  • Measuring module installed in the control compartment

Section 3

600V distribution:

  • Circuit breakers in compartments with exterior operating handles:
    • 6x circuit breakers 25kA 400A 3 poles c/a ST
    • 2x 25kA 200A 3-pole circuit breakers
    • 3x PTO 225A outputs
    • (ST= “Shunt-Trip” magnetic trigger)
  • 600V distribution panel including:
    • 1x main circuit breaker 35kA 1200A 3 poles with “Shunt-Trip”
    • 1x 25kA 600A 3-pole circuit breaker
    • 2x 25kA 400A 3-pole circuit breakers
    • 2x 25kA 200A 3-pole circuit breakers
    • 1x 25kA 30A 3-pole circuit breaker
    • 1x 25kA 15A 3-pole circuit breaker

Enclosure:

  • Transportable vertically
  • NEMA 2 transformer and switch compartment
  • NEMA 2 control compartment
  • Drip-proof housing, designed for mining use
  • Cabinet cleaned with sandblasting and gray epoxy paint
  • Standard replacement parts available and easy to replace (doors, accessories, etc.)
  • Approximate dimensions: 190’’ L x 90’’ D x 94’’ H