Product Catalog

MinePwr-UP-J30524

Demander une soumission

Description

2 MVA Step-up Substation

Electrical specifications

  • Primary protection: 600V - 2500A DS circuit breaker

Transformer:

  • Primary voltage: 480V / 600V
  • Primary BIL : 10kV
  • Secondary voltage: 13 800V
  • Secondary BIL : 95kV
  • Power transformer: 2000kVA
  • Windings: Copper

Secondary distribution:

  • Switch-disconnector 15kV – 600A
    • Instant action mechanism
    • Provision of padlocks
  • Electrically Operated Fixed Type Vacuum Circuit Breaker 15kV 600A 40kA

Auxiliary distribution including:

  • 1x 5kVA - 120/240V distribution
  • 1x distribution board 120/240V 8 circuits
  • Main circuit breaker 1x30A, 2P
  • 8x 1P15A branch circuit breaker

General specifications

  • NEMA 3
  • Dimensions and approximate weight:
      • 105’’ H x 90’’ D x 210’’ W
      • 32 000 lbs
  • Certification : CSA / ESA